Home / Our Products / NLW1 Air Circuit Breaker

Product Catalog

NLW1Air Circuit Breaker

NLW1 series intelligent circuit breaker for power distribution networks with AC 50/60Hz, rated operating voltages of 400V and 690V, and rated current of 200A to 6300A. It meets IEC60947-2.

Call 01001539094 or 01012235710, or message us on WhatsApp.

NLW1 air circuit breaker, stationary type NLW1 air circuit breaker, drawer type
Rated current
200–6300A
Frame sizes
5models
Pole number
3P, 4P
Icu at AC 400V (6300 A frame)
up to 120kA
Standard
IEC60947-2

NLW1 Series

Application

NLW1 series intelligent circuit breaker is mainly suitable for a power distribution network with AC 50/60Hz, rated operating voltages of 400V, 690V, and rated current of 200A to 6300Adistribute power, protect circuit and power devices against overload, under voltage, short circuit, and ground faults. The core part of the circuit breaker adopts intelligent controller with precise selective protection, which can avoid unnecessary power failure so as to improve the reliability, continuity and safety of the power supply system.

The circuit breaker can be widely used in the power distribution system of power stations, factories, mines and modern commercial buildings, especially in intelligent buildings. It is also often used in wind power generation, solar power generation and other green energy filed The circuit breaker meets the IEC60947-2.

WarningThis product must be installed, connected, used and maintained by qualified personnel in ac cordance with the manual.

Type

Installation mode
stationary type drawer type
Operation mode
electric operation, manual operation
Category use
type B
Pole number
3, 4
Type of release device
intelligent controllers, under voltage release trigger and shunt release trigger.

Intelligent type controller function

a. With overload long delay reverse time limit, short delay reverse time limit, short delay fixed time limit , instantaneous action and other protection functions, can be set by the user, composed of the required protection characteristics:

  • b. Ground fault protection function;
  • c. Overload alarm function;
  • d. Test function;
  • e. Overload alarm function;
  • f. Self-diagnostic function;
  • h. MCR function;
  • i. Thermal simulation function;
  • j. Contact loss indication;

Storage Environment

  • The minimum temperature shall not be lower than-25°C, and the maximum temperature shall not exceed + 55°C;
  • The relative temperature (+ 25°C) shall not exceed 95%;
  • Products in the process of transportation,should be handled with specialcare,should not be inverted, should be tried to avoid violent collision.

Working Environment

  • The ambient air temperature is-5°C ~ + 50°C, and the average value of 24h does not exceed + 35°C (except for special orders).
  • The altitude of the installation site shall not exceed 2,000 m.
  • The relative humidity of the air at the installation site shall not exceed 50% when the maximum temperature is +50°C. It can have higher relative humidity at lower temperature. The mean minimum temperature of the wettest month shall not exceed +25°C, and the mean maximum relative humidity of the month shall not exceed 90%, taking into account the condensation occurring on the surface of the product due to temperature changes.
  • The pollution grade is Grade 3.
  • The main circuit of circuit breaker, the under voltage tripping coil and the primary coil of power transformer are installed as IV, while the other auxiliary circuit and control circuit are installed as III.
  • The installation position shall be vertical,and the inclination ineach direction shall not exceed 5.

What is inside

NLW1 Air circuit breaker

NLW1 air circuit breaker and its numbered components
  1. Drawer circuit breaker
  2. Stationary circuit breaker
  3. Front panel
  4. Door frame
  5. Arc chamber
  6. Secondary circuit
  7. Steel cable interlock
  8. Closing electromagnet
  9. Shunt release
  10. Under voltage release
  11. Electro drive energy storage mechanism
  12. Lock
  13. Lever interlock
  14. Intelligent controller
  15. Operating mechanism
  16. Auxiliary switch
  17. Phase partition

Ratings by frame size

Technical Parameters

Quick selection

Rated current and breaking capacity by frame size
ModelRated current In (A)Icu at AC 400V (kA)Icu at AC 690V (kA)
NLW1-1600200, 400, 630, 800, 1000, 1250, 16006550
NLW1-2000400, 630, 800, 1000, 1250, 1600, 20008050
NLW1-32002000, 2500, 2900, 3200, 4000 (increase capacity type)10065
NLW1-40003600, 400010065
NLW1-63004000, 5000, 6300120–

Summary of the full parameter table below. A dash (–) means the catalogue gives no value.

Swipe the table sideways to see all models.

Technical parameter of circuit breaker (see Table 1)

Table 1   Technical Parameters
ModelNLW1-1600NLW1-2000NLW1-3200NLW1-4000NLW1-6300
Rated current In (A)200,400,630 800,1000 1250,1600400,630,800 1000,1250 1600,20002000,2500 2900,3200,4000 (Increase capacity type)3600, 40004000,5000 6300
Neutral pole current rating In (A)100%In100%In100%In50%In50%In
Rated operating voltage Ue (V)AC400/690/800
Pole number3P, 4P
Rated impact withstand voltage Uimp (kV)AC12
Nominal insulation voltage Ui (V)AC1000
Power frequency withstand voltage (V)AC3500
Rated limit short circuit breaking capacity Icu(kA)AC 400V6580100100120
AC 690V50506565-
Rated short circuit breaking capacity Ics (kA)AC 400V55658080100
AC 690V50506565-
Rated short time withstand current Icw/ 1s (kA)AC 400V55506565100
AC 690V50506565-
Category of useB
Full break time (no additional delay)≤30ms
Closing time≤70ms
Electrical life (times)≤3200 1h/20
>3200 1h/10
AC 400V60005000300020001500
AC 690V50004000200015001000
Mechanical life (times)≤2500 1h/20
>2500 1h/10
Maintenance-free1500010000800050002000
Have maintenance20000120001000060002500
Mechanical life of the drawer holder (1h/20times)100010001000600300
Into the line wayUp or down incoming line
Arc distance(mm)0
Installation modeStationary type or Drawer type
Mode of connectionHorizontal wiring or vertical wiringHorizontal wiring

Note: One time of mechanical life of the drawer base refers to when the circuit breaker body is shaken from → "separated" to → "connected" and then to the → "separated" position in the drawer base.

Maximum power loss of circuit breaker incoming and outgoing line (ambient temperature + 50°C)

Table 2   Power loss of incoming and outgoing lines of circuit breaker
ModelFrame current Inm (A)Power loss(W)
3P Drawer type4P Drawer type3P Stationa type4P Stationa type
NLW1- 16001600230306136182
NLW1-20002000395526262350
NLW1- 32003200556742307409
NLW1-40004000660880332450
NLW1-6300630014291905--

Note: Power consumption of the circuit breaker refers to the power consumption of the main circuit measured by the circuit breaker with the rated current at room temperature, excluding the power of other power loss accessories of the circuit breaker. This table data is only for reference and cannot be used as power consumption in actual use of thecircuit breaker.

Altitude reduction coefficient

When the altitude exceeds 2000 meters, the insulation performance, cooling performance and pressure in the atmosphere will change, and its performance can be corrected by referring to Table 4.

Table 4   Coefficient of capacity reduction at altitude
Altitude (m)2000300040005000
Working current Ie10.930.880.82
Short circuit breaking capacity Icu, Ics10.830.710.63
Short circuit tolerance Icw10.830.710.63
Rated impact withstand voltage Uimp10.90.710.63
Power frequency withstand voltage10.90.710.63
Rated insulation voltage Ui10.830.710.63

The recommendation for installing of busbar

Table 5   Recommendation for installing of busbar
Rated current (A)External copper busbar (width*thickness) mmRequired busbar qty per poleCross-sectional area (mm²)
20020×51100
40040×51200
63040×52400
80050×52500
100060×52600
125080×52800
1600100×521000
2000100×531500
2500100×542000
2900100×1033000
3200100×1044000
3600100×1055000
4000100×1055000
5000100×1066000
6300100×1088000

Note:

  1. The specification in the table is that the circuit breaker used in ambient environment of 50°C and installed open.
  2. The material of busbar is T2 bare copper. The specification of the external copper busbar can be changed according to the actual use situation, but it should meet the cross-sectional area requirements corresponding to different currents in the table.

Intelligent controller

Protection Performance

a. Protection performance of the intelligent controller

The over current protection characteristic curve of the intelligent controller is shown in Figure 1.

The setting range I / In and accuracy of the intelligent controller:

Swipe the table sideways to see all columns.

Protection typeLong time delayShort time delayInstantaneousGround protection
Frame gradeIRAccuracyIsdAccuracyIiAccuracyIgAccuracy
NLW1-1600(0.4~1)In±10%(0.4~15)In±10%1In~50kA +OFF±15%(0.2~1)In±10%
NLW1-20001In~50kA +OFF
NLW1-3200/40001In~75kA +OFF
NLW1-63001In~100kA +OFF

b. Long time delay over current protection reverse time limit action characteristics

For the long time delay over current protection, the reverse time limit curve conforms to the characteristic curve of I²TL = (1.5 Ir)² tL. Where I is the actual action current; TL is the actual action time with a long time delay; and tL is the setting time for a long time delay of 1.5 IR.

Swipe the table sideways to see all columns.

Current multipleAction time
1.05IRNo action within 2 h
1.3IR<1h action
1.5IRSetting time(s)153060120240480
2.0IRActuation time(s)8.416.933.767.5135270

c. Short time delay over current protection action characteristics

Swipe the table sideways to see all columns.

CurrentAction time
I≥Isd, I≤8IRInverse time limitI² Ts = (8IR)² ts
I≥Isd, I>8IRFixed time limitSetting time (s)0.10.20.30.4
Action time(s)0.060.140.230.35

Note: a) action time tolerance ± 15%. b) I is the actual action current; ts is the set time for short time delay; and Ts is the actual action time.

d. Short circuit instantaneous protection action characteristics

The instantaneous protection function prevents the load from short circuit in the distribution system. This kind of fault usually happens between phases so the short circuit current is relatively big, which needs to be disconnected quickly.

This protection is executed based on the true effective value of the current. When I≤0.85Ii, I> 1.15 Ii (I is actual short circuit current).

e. The protection characteristics and curve of grounding fault (Figure 2)

There are two kinds of ground fault protection: one is to detect the current of neutral point, when the current of three-phase is in balance, the neutral point current is zero. When the current of three-phase is in imbalance, the current of neutral point exceeds the set value, the intelligent controller alarms, the circuit breaker is disconnected or constantly open according to the instruction after the fixed delay time. The other is to detect the current of the grounding wire, when the current exceeds the set value, the intelligent controller alarms, make the circuit breaker be disconnected or constantly open according to the instruction after the fixed delay time. The grounding fault protection characteristics is fixed time limit.

Action current Set 6Point Ig(0.2~1)In+OFF
Action characteristic≤0.8Ig failure to actuate
≥1.1Ig deferred action
Setting time (s)(0.2~1)In+OFF (OFF That only the alarm is not removed)

f. Self-diagnostic function

The intelligent controller can diagnose its own fault when failure happens to the computer. It can display "E" (means error) or alarm, and restart computer at the same time. The circuit breaker can be disconnected when necessary.

When the local ambient temperature reaches 80°C or the temperature in the casing exceeds 80°C due to the heat of the contact, an alarm can be issued, and the circuit breaker can be switched off at a smaller current (when the user needs).

Figure 1  Over current protection characteristic curve of the intelligent controller
Figure 2  Ground fault protection characteristic curve

g. Load monitoring function

Set two set values Ic1 and Ic2, setting range of both are (0.2~1) In. The delay feature of Ic1 is the reverse time limit characteristic, Its delay setting value is 1 / 2 of the long delay setting value. There are two kinds of delay characteristics for Ic2: one is the reverse time limit characteristics, its value of time setting is 1/ 4 of the long delay setting value; The other is the fixed time limit characteristic, Its delay time is 60s. The first delay function is used to switch off the last important load when the current approaches the set overload value. The latter delay function is used to delay switching off unimportant load to decrease the current in order to maintain the power supply for main circuit and important load circuits when the current exceeds the Ic1 value. When the current drops to Ic2, a command is issued after a delay to reconnect the lower circuit that has been cut off restore the power supply to the entire system. The load monitoring features are shown in the following figure.

Ic1 Load monitoring function
Ic2 Load monitoring function

h. Display function of the controller

The controller can display the operating current and voltage (i. e., ammeter and voltmeter function) during operation.

When the fault occurs, it displays the section specified by its protection characteristics, and latch the fault display and fault current after disconnecting the circuit. During setting, it displays current, time and section type of the section. If it is a delay action, the indicator light will flash during the action.

The indicator light will change from flashing to  constant lighting after the circuit breaker is disconnected. During the test, the test current, delay time, test indication and test action section are displayed.

i. DO signal and alarm function

The controller can output 8 DO output signals for the controller or sound and light alarm indication.The corresponding functions include: overload pre-alarm signal, short circuit tripping signal (short delay and instantaneous), long delay tripping signal, ground tripping or alarm signal, load monitoring 1 signal, load monitoring 2 signal, self-diagnosis alarm signal and fault tripping signal (OCR).

j. MCR and over ultimate trip protection

The MCR and over ultimate trip function is high speed instantaneous protection. The fault current signal sends action command directly through the hardware comparison circuit. MCR protection only works at the moment of switch-on of the circuit breaker (about 100ms), while the over ultimate trip protection always plays a role during operation. MCR protection is to protect the ultimate switching capacity of the circuit breaker to prevent the power grid from being in the short circuit fault state before the switch is switched on. While switching on the circuit breaker, the current generated in the moment will be  bigger than the switching capacity, the controller switches off the circuit breaker in an instantaneous manner. Over ultimate trip protection is to protect the  ultimate load capacity of the circuit breaker, and prevent the circuit breaker from being damaged by  the current exceeding the ultimate load capacity.

k. Thermal memory fuction

Due to overload or short delay tripping, there will be thermal effect which is similar to bimetal in the controller. The overload thermal effect energy is released in 30min while the short delay energy is released in 15min. During this period, if overload or short delay failure occurs again, the disconnection time will become shorter. The controller loses power and eliminates the energy automatically.

Preset value of the intelligent controller

Swipe the table sideways to see all columns.

Table 6  Preset value of the intelligent controller
Controller typeLong delayShort delayInstantaneousGround protectionLoad monitoring
IRtLIsdtLIiIgtGIc1Ic2
NLW1-M1In60s8I R0.2s12I R0.8I ROFF1In
NLW1-2H/3H1In60s8I R0.2s12I R0.8I ROFF1In

Stationary and drawer type

Structure Overview

Stationary type circuit breaker is mainly composed of the contact system, intelligent controller, manual operation mechanism, electric operation mechanism and fixed installation board.

Drawer type circuit breaker is mainly composed of the contact system, intelligent controller, manual operation mechanism, electric operation mechanism and drawer holder.

The contact system is closed in the insulating floor and each phase contact is separated by an insulation board to form a small chamber, while the intelligent controller, the manual operation mechanism and the electric operation mechanism are arranged in front of it, forming independent units. If one of the units is broken, the whole unit can be removed and replaced with a new one. The circuit breaker consists of a body and a fixed bracket, and becomes a stationary type.

Fixed bracket plus circuit breaker body plus fixed bracket equals stationary type circuit breaker

Drawer Type Circuit Breaker

The drawer type circuit breaker is composed of the circuit breaker body and the drawer holder. The guide rail in the drawer holder can be pulled in and out, and the main loop is connected through the bus on the circuit breaker body and the bridge plug on the drawer holder.

The drawer type circuit breaker has three working positions: “connected”, “test” and “separated”. The position is changed by rotating the handle in or out, and the three positions are indicated by the pointer on the drawer seat beam.

  • Connected: the main loop and the secondary loop are connected.
  • Test: the main loop is disconnected and separated by an insulation partition; only the secondary loop is connected, so some necessary action tests can be carried out.
  • Separated: the main loop and the secondary loop are all disconnected.

The drawer type circuit breaker also has a mechanical interlocking device: it can only be switched on in the “connected” or “test” position, and cannot be switched on in the middle position between “connected” and “test”.

There are two types of circuit breakers: drawer type and fixed type

The circuit breaker consists of two parts: the body and the drawer holder, and the body is inserted into the drawer holder.

Intelligent controller mechanical reset button

Reset button in normal operating state
Normal operating state
Reset button popped out after protection trip
When the intelligent controller is in the protected state, the circuit breaker is disconnected and the circuit fault is cleared. Press the button to switch on the circuit breaker again.

Operating state of the operating mechanism

Indicator: open, energy not stored
Circuit breaker is disconnected and no energy storage
Indicator: open, energy stored
Circuit breaker is disconnected and the energy storage state has been completed
Indicator: closed, energy not stored
Circuit breaker switched on and no energy storage
Indicator: closed, energy stored
Circuit breaker switched on and the energy storage state has been completed

Drawer type circuit breaker (Only the Drawer type circuit breakers have this function)

  • Position indicator at connected
    “Connected” position Main circuit and second circuit are connected
  • Position indicator at test
    “Test” position: main circuit is disconnected and second circuit is connected
  • Position indicator at separated
    “Separated” position: Main circuit and seconda
Position lock button on the drawer holder in unlock and lock state
  • After the position is locked, operate the shake handle, press the position lock button to release the lock (unlock state)
  • In the separated state, the connected three positions: the main board is locked, and the shake handle cannot operate (lock state)

There position lock of the drawer holder: lock the circuit breaker body in the drawer holder: "separated", "test" and "connected".

Secondary circuit

Control Loop

Secondary loop wiring diagram of NLW1-1600~6300 with M-type intelligent controller

Secondary-circuit wiring diagram of NLW1-1600~6300 with H-type intelligent controller

The red dotted line in the wiring diagram is wired by the user himself, and the control circuit should be protected by the fuse.
Note: Under voltage release can also be connected frequently closed butt emergency cases.

SymbolParaphraseRemarks
QUnder voltage releaseOptional attachment
FShunt release
XClosing electromagnet
DFAuxiliary switch
SAMotor micro-dynamic switch
MElectric motor
XTTerminal connectorUser self-provided
⊗Signal lampUser self-provided
SB1Manual switch buttonUser self-provided
SB2Manual closing button

Swipe the table sideways to read the full description.

Terminal numberTerminal function descriptionRemarks
1,2Auxiliary power supply input: AC230V, AC400V, DC220V, and DC110VType M default configuration
2H / 3H communication type configuration
3,4,5Fault trip contact output (4 # is the public end), contact capacity: AC250V, 3A
6,7Breaker state auxiliary contact output (often open), contact capacity: AC250V, 3A
8,9Breaker state auxiliary contact output (often open), contact capacity: AC250V, 3A
20Protection area (PE)
10,11Rs485 communication interf ace lead, 10 to A, 11 to B (default Modbus)2H / 3H communication type configuration
12,19Relay contact output: 12 and 13 are DO 1; 14 and 15 are DO 2; 16,17 D 3 for remote switch DO contacts; 18 and 19 DO 4 for remote switch contacts
21,22,23,24Voltage measurement input: 21 N, 22 A, 23 B, 24 C
25,26a: Connect neutral wire transformer for 3P + N; b: Connect leakage transformer for leakage protection (alternative)Optional attachment
27,28Under voltage release (Direct connected to autonomous loop power supply to improve the reliability and security of power supply)Optional attachment
29,30Shunt release
31,32Closing electromagnet
33,34,35Electric motor(35 can be directly connected to the power supply automatic pre-storage, or can connect the power supply manual pre-storage)
36~47Auxiliary switch Terminal terminal (default four ad conversion)

NLW1-2000~6300 Auxiliary swich (DF) type

Outline and mounting size (mm)

Overall Dimension

Choose a frame size, then tap a drawing to enlarge it.

NLW1-1600
NLW1-1600 Fixed Circuit breaker Outline and mounting size (mm)
NLW1-1600
NLW1-1600 drawer type circuit breaker profile with installation size (mm)
NLW1-2000
NLW1-2000 Fixed Circuit breaker Outline and mounting size (mm)
NLW1-2000
NLW1-2000 drawer type circuit breaker profile with installation size (mm)
NLW1-3200
NLW1-3200 Fixed Circuit breaker Outline and mounting size (mm)
NLW1-3200
NLW1-3200 drawer type circuit breaker profile with installation size (mm)
NLW1-4000/3P
NLW1-4000 / 3P Fixed Circuit breaker Outline and mounting size (mm)
NLW1-4000/3P
NLW1-4000 / 3P expansion drawer type circuit breaker profile with installation size (mm)
NLW1-6300/3P
NLW1-6300 Fixed Circuit breaker Outline and mounting size (mm)
NLW1-6300
NLW1-6300 drawer type circuit breaker profile with installation size (mm)

Panel, buttons and settings

Intelligent Controller

The description of panel display and function of the controller

Front panel of the Pyramids intelligent controller
Information on the panelFunction declaration
InRated current of the controller
GCurrent of ground or N phase ( constant light refer to ground, ash refer to N phase)
L1Current of phase A
L2Current of phase B
L3Current of phase C
MAXMaximum phase current
AUnit of current
kAUnit of current
SUnit of time (s)
testSimulated tripping test
Ic1Load monitoring No. 1
Ic2Load monitoring No. 2
δCurrent imbalance protection
IgGround protection
IRLong time delay protection
IsdShort time delay protection
IiInstantaneous protection
WARN / ALARMFault alarm
MEMORYSave information
RUNIn normal operation state
Button Function declaration
CLEANClear the fault display on screen and return to the run state
SETPress the button, then click the button continuously to display all of  parameters in sequence
MEMORYConrm to save when the parameters are set
FUNCTIONAuxiliary function
FAULT CHECKCheck the fault record
TRIPSimulate tripping test
NO TRIPSimulated non-tripping test
▲ +Adjust the set parameter value to be increased
▼ −Adjust the set parameter value to be decreased

How to set the parameters of  the intelligent controller

Use those four buttons on the controller panel: SET , ▲ + , ▼ − , MEMORY to set all the parameters of the controller.

The basic steps are described as follows:

  1. ① Click the button of " SET " continuously to check all of  parameters in sequence periodically. When a parameter is checked, the original set value of the parameter is displayed on the screen, and the corresponding indicator on the panel will be light on. If you do not need to change this parameter, go on clicking the butt on of " SET ".
  2. ② If you need to change the original set parameter, click the button of " ▲ + "or" ▼ − " continuously. In the process of setting for current, in order to get the required set  value quickly, the user can click the button of "function" to converse the mode of adjustment between fast adjustment code and fine adjustment code until the required value is achieved.
  3. ③ Press button of " MEMORY " to save the new set parameters. If no other parameters are required to be set, follow the step mentioned in ④ to exit the set. Otherwise, continue according to the step mentioned in ① .
  4. ④ Press the button of " CLEAN " to exit the setting state.

All the protection parameters of the controller should be set according to Ir1 <Ir 2 <Ir 3 strictly.

Simulation test operation of the controller

Simulation characteristics test against grounded, long delay, short delay and nstantaneous can be oper ated for the controller. Two kinds of test are available: tripping and non-tripping. The first one needs to break the circuit breaker, the second one does not break the circuit breaker. If faults such as overload or short circuit occurs during the test, the system will automatically terminate the test state and turn to the fault processing state.

Get the full NLW1 catalog

Download the PDF catalog, or send us your rated current, pole number and installation mode and our team will prepare a quotation.